260-3098-010

Circuit Breakers

CIRCUIT BREAKER

260-3098-010

5925-00-479-7442

5925 - Circuit Breakers

Rockwell Collins Inc.

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Ultimate Trip Time Per Pole In Seconds

    1500.000 minimum all locations

  • Body Width

    4.125 inches nominal

  • Switch Current Rating And Type In Amps

    1.5 ac

  • Reset Method

    manual

  • Switch Location And Position Designation

    internal at pole three

  • Body Length

    6.500 inches nominal

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Switch Terminal Type

    wire lead

  • Internal Trip Release Configuration

    series trip all locations

  • Switch Voltage Rating And Type In Volts

    600.0 ac

  • Maximum Continuous Load Current Rating Per Pole

    100.0 amperes ac all locations and 100.0 amperes dc all locations

  • Body Height

    3.188 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    5.562 inches nominal

  • Boss Height

    0.187 inches nominal

  • Inclosure Protection Type For Which Designed

    shockproof and moisture resistant and vibrationproof

  • Actuator Position Designation

    at pole two

  • Switch Contact Arrangement

    single pole, double throw

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    100.0 all locations

  • Body Style

    multipole-single actuator type

  • Manual Actuator Type And Quantity

    1 toggle

  • Center To Center Distance Between Terminals Parallel To Length

    4.938 inches nominal

  • Frequency In Hertz

    60.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Terminal Type And Quantity

    6 screw

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations

  • Unthreaded Mounting Hole Diameter

    0.188 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    2.750 inches nominal

  • Trip Release Ambient Temp Rating

    55.0 deg celsius maximum all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    480.0 ac all locations and 250.0 dc all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    17.000 minimum at 200 pct all locations and 30.000 maximum at 200 pct all locations

  • Auxiliary Switch Function And Quantity

    1 control

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.376 inches nominal

  • Trip Release Method

    thermal all locations

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...