AM12HKMG6-5-250-400-14

Circuit Breakers

CIRCUIT BREAKER

AM12HKMG6-5-250-400-14

5925-00-479-7911

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    single pole type

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.062 inches nominal

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Storage Type

    general purpose warehouse

  • Thread Quantity Per Inch

    32

  • Switch Contact Arrangement

    single pole,double throw

  • Boss Height

    0.140 inches nominal

  • Mounting Surface To Terminal End Distance

    2.471 inches nominal

  • Pole Quantity

    1

  • Maximum Continuous Load Current Rating Per Pole

    5.0 amperes ac

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac

  • Circuit Protection Type

    overcurrent

  • Trip Release Method

    magnetic-hydraulic

  • Trip Release Characteristic

    time delay

  • Ultimate Trip Time Per Pole In Seconds

    70.000 minimum and 400.000 maximum

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Actuator Position Designation

    at pole one

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Switch Current Rating And Type In Amps

    5.0 ac and 1.0 dc

  • Switch Voltage Rating And Type In Volts

    125.0 ac and 50.0 dc

  • Frequency In Hertz

    400.0

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0

  • Internal Trip Release Configuration

    series trip

  • Nominal Thread Size

    0.138 inches

  • Switch Location And Position Designation

    internal at pole one

  • Trip Delay Time In Seconds Per Rated Continuous Current

    26.000 minimum at 200 pct and 80.000 maximum at 200 pct

  • Inclosure Protection Type For Which Designed

    explosion resistant and fungus resistant and moisture resistant

  • Switch Terminal Type

    tab,solder lug

  • Thread Series Designator

    unc

  • Terminal Type And Quantity

    2 threaded stud

  • Body Length

    2.500 inches nominal

  • Body Width

    0.750 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    1.938 inches nominal

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...