63213-7
Circuit Breakers
CIRCUIT BREAKER
63213-7
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Switch Terminal Type
tab, solder lug
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Body Width
0.750 inches nominal
-
Actuator Function
trip-reset
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes ac single location and 3.0 amperes dc single location
-
Precious Material
gold
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
145.0 single location
-
Thread Quantity Per Inch
32
-
Unpackaged Unit Weight
1.000 ounces
-
Circuit Protection Type
overcurrent single location
-
Bushing Length
0.359 inches nominal
-
Trip Release Method
thermal single location
-
Switch Current Rating And Type In Amps
2.0 ac and 3.0 dc
-
Manual Actuator Type And Quantity
1 push-pull
-
Pole Quantity
1
-
Mounting Surface To Terminal End Distance
1.420 inches maximum
-
Case Material
plastic
-
Thread Series Designator
uns
-
Switch Location And Position Designation
internal at pole one
-
Center To Center Distance Between Terminals Parallel To Length
0.593 inches nominal
-
Inclosure Protection Type For Which Designed
fungus resistant and explosion proof
-
Nominal Thread Size
0.469 inches
-
Auxiliary Switch Function And Quantity
1 alarm
-
Terminal Type And Quantity
2 tab w/screw
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location and 30.0 dc single location
-
Switch Voltage Rating And Type In Volts
120.0 ac and 30.0 dc
-
Switch Contact Arrangement
single pole, single throw, normally open
-
Body Style
single pole type
-
Frequency In Hertz
400.0 single location
-
Body Length
1.287 inches minimum and 1.317 inches maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Trip Release Characteristic
time delay single location
-
Precious Material And Location
auxiliary terminals gold
-
Internal Trip Release Configuration
series trip single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 minimum at 200 pct single location and 20.000 maximum at 200 pct single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2500.0 ac single location and 2500.0 dc single location