17-03977-1

Circuit Breakers

CIRCUIT BREAKER

17-03977-1

5925-00-498-8340

5925 - Circuit Breakers

Textron Systems Corporation

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Fragility Factor

    moderately rugged

  • Trip Release Characteristic

    instantaneous all locations

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Reset Method

    manual

  • Features Provided

    adjustable trip release

  • Operating Voltage Type And Rating Per Pole In Volts

    500.0 ac all locations and 250.0 dc all locations

  • Maximum Continuous Load Current Rating Per Pole

    225.0 amperes ac all locations and 225.0 amperes dc all locations

  • Storage Type

    general purpose warehouse

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal all locations

  • Actuator Function

    trip-reset

  • Mounting Surface To Terminal End Distance

    9.687 inches nominal

  • Body Width

    9.000 inches maximum

  • Body Length

    15.500 inches maximum

  • Unthreaded Mounting Hole Diameter

    0.250 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    3.000 inches nominal

  • Trip Release Method

    thermal-magnetic all locations

  • Actuator Position Designation

    at pole two

  • Inclosure Protection Type For Which Designed

    fungus resistant

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    14.625 inches nominal

  • Body Style

    multipole-single actuator type

  • Boss Height

    0.250 inches nominal

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Manual Actuator Type And Quantity

    1 toggle

  • Frequency In Hertz

    60.0 all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    3.000 inches nominal

  • Main Contact Tripping Mechanism Type

    trip free

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    20000.0 ac all locations and 15000.0 dc all locations

  • Adjustable Trip Setting Current Range Per Pole In Amps

    +1800.0/+2100.0 ac all locations and +1800.0/+2100.0 dc all locations

  • Center To Center Distance Between Terminals Parallel To Length

    12.750 inches nominal

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...