D6750-2-30
Circuit Breakers
CIRCUIT BREAKER
D6750-2-30
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Inclosure Protection Type For Which Designed
dustproof
-
Thread Series Designator
unc
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac single location and 30.0 amperes dc single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location and 1000.0 dc single location
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal single location
-
Terminal Type And Quantity
2 screw
-
Mounting Facility Type And Quantity
2 threaded hole
-
Overall Width
0.750 inches nominal
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Pole Quantity
1
-
Trip Delay Time In Seconds Per Rated Continuous Current
3600.000 nominal at 125 pct single location and 28.000 nominal at 300 pct single location
-
Nominal Thread Size
0.138 inches
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Operating Voltage Type And Rating Per Pole In Volts
30.0 ac single location and 30.0 dc single location
-
Overall Height
3.266 inches nominal
-
Overall Length
2.250 inches nominal
-
Reset Method
automatic
-
Case Material
plastic