MIL-C-55629/6

Circuit Breakers

CIRCUIT BREAKER

MIL-C-55629/6

5925-00-503-8505

5925 - Circuit Breakers

Military Specifications

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • ~1

    type data on certain environmental and performan

  • Pole Quantity

    3

  • Fragility Factor

    moderately rugged

  • Inclosure Protection Type For Which Designed

    fungus resistant and salt spray proof and shock resistant and moisture resistant and vibration resistant

  • Center To Center Distance Between Terminals Parallel To Width

    0.750 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    1.660 inches minimum and 1.960 inches maximum

  • Special Handling Feature

    magnetic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.750 inches nominal

  • Arc Quenching Method

    magnetic blowout

  • Boss Height

    0.140 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    15.0 amperes ac all locations

  • Switch Terminal Type

    knife blade

  • Frequency In Hertz

    400.0 all locations

  • Thread Pitch Diameters

    +0.1177/+0.1214 inches

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Manual Actuator Type And Quantity

    3 toggle

  • Case Material

    plastic

  • Terminal Type And Quantity

    6 threaded stud

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.046 inches minimum and 2.078 inches maximum

  • Switch Location And Position Designation

    internal at pole three

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Trip Delay Time In Seconds Per Rated Continuous Current

    20.000 minimum at 200 pct all locations and 80.000 maximum at 200 pct all locations

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Specification/Standard Data

    81349mil-prf-55629/6 government specification

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Body Length

    2.530 inches maximum

  • Thread Quantity Per Inch

    32

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac all locations

  • Body Width

    2.205 inches minimum and 2.285 inches maximum

  • Trip Release Method

    magnetic all locations

  • Switch Current Rating And Type In Amps

    10.0 ac and 2.0 dc

  • Body Style

    multipole-multiple actuator type

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Mounting Surface To Terminal End Distance

    2.800 inches maximum

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Nominal Thread Size

    0.138 inches

  • Main Contact Tripping Mechanism Type

    trip free

  • Test Data Document

    81349mil-prf-55629 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...