70-613-1AMP
Circuit Breakers
CIRCUIT BREAKER
70-613-1AMP
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
2.500 inches nominal
-
Body Width
0.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
1.938 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Mounting Surface To Terminal End Distance
2.471 inches nominal
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
1.0 amperes ac single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2000.0 ac single location
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 single location
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Internal Trip Release Configuration
series trip single location
-
Frequency In Hertz
60.0 single location
-
Thread Series Designator
unc
-
Body Style
12a single pole type
-
Case Material
plastic
-
Boss Height
0.140 inches nominal
-
Pole Quantity
1
-
Operating Voltage Type And Rating Per Pole In Volts
115.0 ac single location
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
magnetic-hydraulic single location
-
Ultimate Trip Time Per Pole In Seconds
7.000 minimum single location and 29.000 maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
3.000 minimum at 200 pct single location and 9.500 maximum at 200 pct and 1.000 minimum at 300 pct and 4.000 maximum at 300 pct and 0.500 minimum at 400 pct and 2.000 maximum at 400 pct
-
Inclosure Protection Type For Which Designed
fungus resistant and explosion resistant
-
Terminal Type And Quantity
2 threaded stud