TF126070
Circuit Breakers
CIRCUIT BREAKER
TF126070
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
400.000 minimum at 125 pct all locations and 52.000 minimum at 200 pct all locations and 21.000 minimum at 300 pct all locations and 6000.000 maximum at 125 pct all locations and 135.000 maximum at 200 pct all locations and 42.000 maximum at 300 pct all
-
~1
locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
122.0 all locations
-
Circuit Protection Type
overcurrent all locations
-
Overall Height
4.812 inches nominal
-
Pole Quantity
2
-
Actuator Function
trip w/separate reset
-
Reset Method
manual
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Terminal Type And Quantity
4 screw
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations
-
Overall Width
2.750 inches nominal
-
Trip Release Method
thermal-magnetic all locations
-
Unthreaded Mounting Hole Diameter
0.281 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
70.0 amperes ac all locations and 70.0 amperes dc all locations
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Arc Quenching Method
deion
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Mounting Facility Type And Quantity
2 unthreaded hole
-
Main Contact Tripping Mechanism Type
trip free
-
Trip Release Duty Cycle
continuous all locations
-
Overall Length
9.375 inches nominal
-
Special Features
mtg holes spaced 7.250 in. c to c
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac all locations and 15000.0 dc all locations
-
Case Material
plastic