WP115WC375
Circuit Breakers
CIRCUIT BREAKER
WP115WC375
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Reset Method
manual
-
Internal Trip Release Configuration
relay trip single location
-
Actuator Function
trip-reset
-
Terminal Type And Quantity
2 screw
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Unthreaded Mounting Hole Diameter
0.250 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
19.000 nominal at 200 pct single location and 29.000 nominal at 125 pct single location and 6.600 nominal at 300 pct single location
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location
-
Pole Quantity
1
-
Case Material
metal
-
Nondefinitive Spec/Std Data
w+115 type
-
Manual Actuator Type And Quantity
1 toggle
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac single location
-
Mounting Facility Type And Quantity
2 unthreaded hole
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location
-
Trip Release Characteristic
instantaneous single location and time delay single location