3XAM1516MG3-60-250-2-50
Circuit Breakers
CIRCUIT BREAKER
3XAM1516MG3-60-250-2-50
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Body Length
3.719 inches nominal
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Mounting Surface To Terminal End Distance
3.359 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.031 inches nominal
-
Thread Quantity Per Inch
32
-
Ultimate Trip Time Per Pole In Seconds
20.000 minimum all locations and 65.000 maximum all locations
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Center To Center Distance Between Terminals Parallel To Length
3.063 inches nominal
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Body Width
3.052 inches nominal
-
Mounting Facility Type And Quantity
6 threaded hole
-
Nominal Thread Size
0.138 inches
-
Boss Height
0.156 inches nominal
-
Frequency In Hertz
50.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
60.0 amperes ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
18.000 maximum at 200 pct all locations and 0.600 minimum at 500 pct all locations and 5.000 minimum at 200 pct all locations and 1.700 maximum at 500 pct all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Manual Actuator Type And Quantity
3 toggle
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.031 inches nominal
-
Case Material
plastic
-
Terminal Type And Quantity
6 threaded stud