6761-1-5
Circuit Breakers
CIRCUIT BREAKER
6761-1-5
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Body Width
0.750 inches nominal
-
Actuator Function
trip-reset
-
Terminal Type And Quantity
2 screw
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac single location
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Trip Release Method
thermal single location
-
Mounting Facility Type And Quantity
1 threaded bushing
-
Operating Voltage Type And Rating Per Pole In Volts
200.0 ac single location
-
Manual Actuator Type And Quantity
1 push-pull
-
Pole Quantity
1
-
Inclosure Protection Type For Which Designed
explosion proof and fungus resistant
-
Internal Trip Release Configuration
series trip single location
-
Trip Release Characteristic
time delay single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Bushing Length
0.469 inches nominal
-
Body Length
1.094 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
100.000 nominal at 200 pct single location and 20.000 nominal at 300 pct single location
-
Body Style
single pole type
-
Mounting Surface To Terminal End Distance
3.062 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 single location
-
Unpackaged Unit Weight
8.000 ounces
-
Frequency In Hertz
60.0 single location
-
Nominal Thread Size
0.469 inches
-
Thread Series Designator
uns
-
Case Material
plastic
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location
-
Reset Method