ETN1078
Circuit Breakers
CIRCUIT BREAKER
ETN1078
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Test Data Document
81349-mil-c-17588 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
~1
data on certain environmental and performanc
-
Specification/Standard Data
81349-mil-c-17588 government specification
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Maximum Continuous Load Current Rating Per Pole
50.0 amperes ac single location and 50.0 amperes dc single location
-
Manual Actuator Type And Quantity
1 toggle
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal single location
-
Trip Release Method
thermal-magnetic single location
-
Body Length
3.500 inches nominal
-
Boss Height
0.188 inches nominal
-
Trip Release Characteristic
time delay single location
-
Main Contact Tripping Mechanism Type
trip free
-
Precious Material And Location
contact surfaces silver
-
Frequency In Hertz
400.0 single location
-
Terminal Type And Quantity
1 compression and 1 quick disconnect, female
-
Body Style
single pole type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 single location
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location and 125.0 dc single location
-
Case Material
plastic
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Precious Material
silver
-
Storage Type
general purpose warehouse
-
Body Height
2.312 inches nominal
-
Actuator Function
trip-reset
-
Mounting Facility Type And Quantity
1 terminal and 1 clip
-
Body Width
0.906 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac single location and 5000.0 dc single location
-
Inclosure Protection Type For Which Designed
vibration resistant and shock resistant
-
Circuit Protection Type
overcurrent single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 200 pct single location and 210.000 maximum at 200 pct single location
-
Pole Quantity
1