S1332274
Circuit Breakers
TRIPPER,CIRCUIT BREAKER
S1332274
TRIPPER,CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 terminal
-
Circuit Protection Type
overcurrent all locations
-
Body Style
rectangular dimensional envelope
-
Maximum Continuous Load Current Rating Per Pole
200.0 amperes ac all locations
-
Overall Width
3.875 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations
-
Terminal Type And Quantity
6 bus bar
-
Adjustable Trip Setting Current Range Per Pole In Amps
+600.0/+2000.0 ac all locations
-
Features Provided
adjustable trip release
-
Trip Delay Time In Seconds Per Rated Continuous Current
498.000 maximum at 200 pct all locations and 30.000 minimum at 300 pct all locations and 99.600 minimum at 200 pct all locations and 138.000 maximum at 300 pct all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal all locations
-
Frequency In Hertz
60.0 all locations
-
Overall Length
7.438 inches nominal
-
Overall Height
3.250 inches nominal