NE113015
Circuit Breakers
CIRCUIT BREAKER
NE113015
Challenger Electrical Equipment Corp
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Thread Series Designator
unc
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal single location
-
Terminal Type And Quantity
2 screw
-
Mounting Facility Type And Quantity
2 threaded hole
-
Center To Center Distance Between Terminals Parallel To Length
5.000 inches nominal
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
7500.0 ac single location and 5000.0 dc single location
-
Body Length
6.219 inches nominal
-
Inclosure Protection Type For Which Designed
fungus resistant
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
5.312 inches nominal
-
Body Width
1.375 inches nominal
-
Pole Quantity
1
-
Manual Actuator Type And Quantity
1 toggle
-
Nominal Thread Size
0.138 inches
-
Trip Release Method
thermal-magnetic single location
-
Trip Release Characteristic
time delay single location
-
Body Height
3.781 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac single location and 15.0 amperes dc single location
-
Body Style
single pole type
-
Frequency In Hertz
60.0 single location
-
Trip Delay Time In Seconds Per Rated Continuous Current
11.000 minimum at 200 pct single location and 35.000 maximum at 200 pct single location
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location and 125.0 dc single location
-
Case Material
plastic