260-4742-000

Circuit Breakers

CIRCUIT BREAKER

260-4742-000

5925-00-552-5959

5925 - Circuit Breakers

Rockwell Collins Inc.

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    10b multipole-single actuator type

  • Body Width

    4.750 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Width

    1.500 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.250 inches nominal and 0.406 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.250 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.500 inches nominal

  • Boss Height

    0.312 inches nominal

  • Mounting Surface To Terminal End Distance

    6.812 inches nominal

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Operating Voltage Type And Rating Per Pole In Volts

    125.0 ac and 125.0 dc all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Trip Release Characteristic

    instantaneous and time delay all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Actuator Position Designation

    at pole two

  • Internal Trip Release Configuration

    series trip first location

  • Internal Trip Release Configuration

    series trip second location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.050 nominal at 200 pct all locations

  • Special Features

    auxiliary switch connected in series w/shunt trip coil

  • Frequency In Hertz

    60.0

  • Body Length

    5.000 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    3.625 inches nominal

  • Switch Contact Arrangement

    single pole, single throw, normally open

  • Pole Quantity

    3

  • Maximum Continuous Load Current Rating Per Pole

    200.0 amperes ac and 200.0 amperes dc all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    10000.0 ac and 5000.0 dc all locations

  • Circuit Protection Type

    overcurrent all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    138.0

  • Reset Method

    manual

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Auxiliary Switch Function And Quantity

    1 control

  • Internal Trip Release Configuration

    shunt trip third location

  • Terminal Type And Quantity

    7 threaded stud

  • Switch Voltage Rating And Type In Volts

    125.0 ac and 125.0 dc

  • Switch Current Rating And Type In Amps

    10.0 ac and 10.0 dc

  • Switch Terminal Type

    tab, solder lug

  • Trip Release Ambient Temp Rating

    50.0 deg celsius nominal all locations

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant

  • Switch Location And Position Designation

    internal at pole three

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...