NEF421060R
Circuit Breakers
CIRCUIT BREAKER
NEF421060R
Challenger Electrical Equipment Corp
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
6.219 inches nominal
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
5.312 inches nominal
-
Pole Quantity
2
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
60.0 amperes ac and 60.0 amperes dc
-
Operating Voltage Type And Rating Per Pole In Volts
480.0 ac and 250.0 dc
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
25.000 minimum at 200 pct and 75.000 maximum at 200 pct
-
Thread Series Designator
unc
-
Bushing Length
0.250 inches nominal
-
Body Width
2.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
5.312 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
1.375 inches nominal
-
Mounting Surface To Terminal End Distance
3.781 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
15000.0 ac and 10000.0 dc
-
Circuit Protection Type
overcurrent
-
Trip Release Method
thermal-magnetic
-
Trip Release Characteristic
instantaneouss and time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 rotary
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal
-
Frequency In Hertz
60.0
-
Terminal Type And Quantity
4 compression