61-593BMG4-16-32

Circuit Breakers

CIRCUIT BREAKER

61-593BMG4-16-32

5925-00-581-6021

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Center To Center Distance Between Terminals Parallel To Width

    0.990 inches minimum and 1.010 inches maximum

  • Frequency In Hertz

    60.0 all locations

  • Inclosure Protection Type For Which Designed

    dustproof and fungus proof

  • Actuator Position Designation

    between pole one and two

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Mounting Facility Type And Quantity

    4 unthreaded hole and 4 threaded hole

  • Nominal Thread Size

    0.164 inches

  • Center To Center Distance Between Terminals Parallel To Length

    4.349 inches minimum and 4.369 inches maximum

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.974 inches minimum and 0.994 inches maximum

  • Fragility Factor

    moderately rugged

  • Special Handling Feature

    magnetic

  • Circuit Protection Type

    overcurrent all locations

  • Pole Quantity

    2

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.349 inches minimum and 4.369 inches maximum

  • Thread Series Designator

    unc

  • Reset Method

    manual

  • Boss Height

    0.208 inches minimum and 0.228 inches maximum

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • Internal Trip Release Configuration

    series trip all locations

  • Maximum Continuous Load Current Rating Per Pole

    32.0 amperes ac all locations

  • Body Height

    2.677 inches minimum and 2.697 inches maximum

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic-hydraulic all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.200 minimum at 200 pct all locations and 0.700 maximum at 200 pct all locations

  • Body Style

    multipole-single actuator type

  • Terminal Type And Quantity

    4 compression

  • Manual Actuator Type And Quantity

    1 toggle

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Body Width

    2.990 inches minimum and 3.010 inches maximum

  • Body Length

    5.240 inches minimum and 5.260 inches maximum

  • Unthreaded Mounting Hole Diameter

    0.190 inches nominal

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...