APG66-1-6-1-103
Circuit Breakers
CIRCUIT BREAKER
APG66-1-6-1-103
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
multipole-single actuator type
-
Body Width
1.500 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.530 inches nominal
-
Mounting Surface To Terminal End Distance
2.032 inches maximum
-
Pole Quantity
2
-
Mounting Facility Type And Quantity
4 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac
-
Circuit Protection Type
overcurrent
-
Actuator Function
trip-reset
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.130 minimum at 200 pct and 0.220 maximum at 200 pct
-
Thread Series Designator
unc
-
Terminal Type And Quantity
4 screw
-
Bushing Length
0.130 inches nominal
-
Body Length
2.000 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.660 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at each pole
-
Frequency In Hertz
60.0