501A302
Circuit Breakers
CIRCUIT BREAKER
501A302
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Method
magnetic single location
-
Mounting Surface To Terminal End Distance
1.524 inches minimum and 1.586 inches maximum
-
Inclosure Protection Type For Which Designed
dustproof
-
Body Width
0.567 inches minimum and 0.629 inches maximum
-
Reset Method
manual
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Actuator Position Designation
at pole one
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Nominal Thread Size
0.375 inches
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 dc single location
-
Body Length
1.448 inches minimum and 1.510 inches maximum
-
Circuit Protection Type
overcurrent single location
-
Bushing Length
0.360 inches minimum and 0.380 inches maximum
-
Pole Quantity
1
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Arc Quenching Method
magnetic blowout
-
Terminal Type And Quantity
2 wire lead
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes dc single location
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc single location
-
Body Style
single pole type
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.140 nominal at 300 pct single location
-
Thread Series Designator
unef
-
Center To Center Distance Between Terminals Parallel To Length
0.870 inches minimum and 0.880 inches maximum
-
Trip Release Characteristic
instantaneous single location and time delay single location