MILC17361
Circuit Breakers
CIRCUIT BREAKER
MILC17361
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
9.875 inches nominal
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Inclosure Protection Type For Which Designed
shock resistant and vibration resistant
-
Precious Material And Location
contacts silver
-
Reset Method
manual
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations and 250.0 dc all locations
-
Center To Center Distance Between Terminals Parallel To Length
9.875 inches nominal
-
Precious Material
silver
-
Storage Type
general purpose warehouse
-
Actuator Function
trip-reset
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Arc Quenching Method
air
-
Unthreaded Mounting Hole Diameter
0.250 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Release Method
thermal-magnetic all locations
-
Body Width
9.000 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
300.000 minimum at 200 pct all locations and 900.000 maximum at 200 pct all locations
-
Body Height
4.625 inches nominal
-
Features Provided
adjustable trip release and interchangeable trip release
-
Actuator Position Designation
at pole two
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Body Style
multipole-single actuator type
-
Center To Center Distance Between Terminals Parallel To Width
1.000 inches nominal
-
Boss Height
0.250 inches nominal
-
Manual Actuator Type And Quantity
1 toggle
-
Frequency In Hertz
60.0 all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.000 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Body Length
11.000 inches nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
20000.0 ac all locations and 20000.0 dc all locations
-
Terminal Type And Quantity
6 threaded stud and 6 tab w/screw
-
Adjustable Trip Setting Current Range Per Pole In Amps
+650.0/+1300.0 dc all locations
-
Maximum Continuous Load Current Rating Per Pole
250.0 amperes ac all locations and 250.0 amperes dc all locations
-
Case Material
plastic