ET4016

Circuit Breakers

CIRCUIT BREAKER

ET4016

5925-00-660-3812

5925 - Circuit Breakers

Spd Electrical Systems Inc

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Style

    11b multipole-single actuator type

  • Body Length

    6.000 inches nominal

  • Body Width

    3.000 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.500 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.594 inches nominal

  • Boss Height

    0.219 inches nominal

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    20000.0 ac and 10000.0 dc all locations

  • Circuit Protection Type

    overcurrent all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    105.0

  • Reset Method

    manual

  • Actuator Position Designation

    at pole one

  • Trip Delay Time In Seconds Per Rated Continuous Current

    22.500 minimum at 200 pct and 30.000 maximum at 200 pct all locations

  • Body Height

    3.594 inches nominal

  • Case Material

    plastic

  • Center To Center Distance Between Terminals Parallel To Length

    4.594 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.190 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.500 inches nominal

  • Pole Quantity

    2

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Storage Type

    general purpose warehouse

  • Maximum Continuous Load Current Rating Per Pole

    70.0 amperes ac and 70.0 amperes dc all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    600.0 ac and 250.0 dc all locations

  • Trip Release Characteristic

    instantaneous and time delay all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Inclosure Protection Type For Which Designed

    general purpose

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal all locations

  • Frequency In Hertz

    60.0

  • Terminal Type And Quantity

    4 compression

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.