AM12MG6-15-250VAC60C4
Circuit Breakers
CIRCUIT BREAKER
AM12MG6-15-250VAC60C4
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.938 inches nominal
-
Boss Height
0.140 inches nominal
-
Mounting Facility Type And Quantity
2 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac
-
Circuit Protection Type
overcurrent
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Position Designation
at pole one
-
Internal Trip Release Configuration
series trip
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 150 pct and 30.000 maximum at 150 pct and 4.000 minimum at 200 pct and 10.000 maximum at 200 pct and 1.400 minimum at 300 pct and 4.000 maximum at 300 pct
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant and explosion resistant
-
Thread Series Designator
unc
-
Terminal Type And Quantity
2 threaded stud
-
Body Length
2.500 inches nominal
-
Body Width
0.750 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Mounting Surface To Terminal End Distance
2.471 inches nominal
-
Pole Quantity
1
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Ultimate Trip Time Per Pole In Seconds
18.000 minimum and 70.000 maximum
-
Reset Method
manual
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Nominal Thread Size
0.138 inches
-
Frequency In Hertz
60.0