MILC17361
Circuit Breakers
CIRCUIT BREAKER
MILC17361
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Test Data Document
81349-mil-c-17361 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
22.000 inches maximum
-
Circuit Protection Type
overcurrent all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
20000.0 dc all locations
-
Pole Quantity
2
-
Reset Method
manual
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Body Length
17.500 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
6.000 inches nominal
-
Body Width
9.000 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
60.000 18 stage minor all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Body Style
multipole-single actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
4 unthreaded hole
-
Mounting Surface To Terminal End Distance
13.187 inches nominal
-
Unthreaded Mounting Hole Diameter
0.438 inches nominal
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
2.750 nominal inches
-
Terminal Type And Quantity
4 pin
-
Internal Trip Release Configuration
relay trip all locations
-
Case Material
plastic
-
Maximum Continuous Load Current Rating Per Pole
600.0 amperes dc all locations
-
Trip Release Method
thermal all locations
-
~1
data on certain environmental and performanc