Technical Characteristics
-
Arc Quenching Method
deion
-
Mounting Facility Type And Quantity
2 unthreaded hole
-
Maximum Continuous Load Current Rating Per Pole
20.0 amperes dc
-
Overall Length
6.000 inches nominal
-
Overall Height
3.594 inches nominal
-
Overall Width
3.000 inches nominal
-
Case Material
plastic
-
Unthreaded Mounting Hole Diameter
0.164 inches nominal
-
Pole Quantity
2
-
Operating Voltage Type And Rating Per Pole In Volts
125.0 dc
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Trip Delay Time In Seconds Per Rated Continuous Current
24.000 minimum at 200 pct and 60.000 maximum at 200 pct and 8.000 minimum at 300 pct and 15.000 maximum at 300 pct
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc
-
Circuit Protection Type
overcurrent
-
Trip Release Method
thermal
-
Trip Release Characteristic
time delay
-
Reset Method
manual
-
Actuator Function
trip w/separate reset
-
Special Features
mtg holes spaced 4.594 in. c to c
-
Terminal Type And Quantity
4 screw