1632-943

Circuit Breakers

CIRCUIT BREAKER

1632-943

5925-00-681-6086

5925 - Circuit Breakers

Westinghouse Electric Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Mounting Facility Type And Quantity

    6 unthreaded hole

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    7500.0 ac and 5000.0 dc

  • Circuit Protection Type

    overcurrent

  • Trip Release Characteristic

    instantaneous and time delay

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Trip Delay Time In Seconds Per Rated Continuous Current

    300.000 nominal at 125 pct and 28.000 nominal at 200 pct and 6.000 nominal at 300 pct

  • Trip Release Ambient Temp Rating

    25.0 deg celsius nominal

  • Frequency In Hertz

    60.0

  • Unthreaded Mounting Hole Diameter

    0.188 inches nominal

  • Pole Quantity

    3

  • Maximum Continuous Load Current Rating Per Pole

    70.0 amperes ac and 70.0 amperes dc

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac and 250.0 dc

  • Trip Release Method

    thermal-magnetic

  • Reset Method

    manual

  • Main Contact Tripping Mechanism Type

    trip free

  • Terminal Type And Quantity

    6 screw

  • Case Material

    plastic

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...