MP160
Circuit Breakers
CIRCUIT BREAKER
MP160
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Actuator Function
reset
-
Trip Release Method
magnetic single location
-
Arc Quenching Method
air
-
Manual Actuator Type And Quantity
1 push-pull
-
Pole Quantity
1
-
Trip Delay Time In Seconds Per Rated Continuous Current
55.000 maximum at 200 pct single location and 15.000 minimum at 200 pct single location and 2.000 minimum at 400 pct single location and 7.000 maximum at 400 pct single location
-
Trip Release Characteristic
time delay single location
-
Trip Release Ambient Temp Rating
25.0 deg celsius nominal single location
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Facility Type And Quantity
2 threaded stud
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac single location and 6000.0 dc single location
-
Maximum Continuous Load Current Rating Per Pole
60.0 amperes ac single location and 60.0 amperes dc single location
-
Overall Length
2.578 inches nominal
-
Reset Method
manual
-
Overall Height
2.188 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.813 inches nominal
-
Terminal Type And Quantity
2 screw
-
Overall Width
0.750 inches nominal
-
Circuit Protection Type
overcurrent single location
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac single location and 30.0 dc single location
-
Case Material
plastic