3XAM17-1.5
Circuit Breakers
CIRCUIT BREAKER
3XAM17-1.5
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Delay Time In Seconds Per Rated Continuous Current
3.000 minimum at 200 pct all locations and 40.000 maximum at 200 pct all locations
-
Mounting Facility Type And Quantity
6 threaded hole
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Nominal Thread Size
0.138 inches
-
Main Contact Tripping Mechanism Type
trip free
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Arc Quenching Method
magnetic blowout
-
Mounting Surface To Terminal End Distance
2.010 inches maximum
-
Bushing Length
0.125 inches nominal
-
Frequency In Hertz
400.0 all locations
-
Maximum Continuous Load Current Rating Per Pole
1.15 amperes ac first location
-
Body Length
2.510 inches maximum
-
Terminal Type And Quantity
6 tab w/screw
-
Maximum Continuous Load Current Rating Per Pole
1.15 amperes ac third location
-
Manual Actuator Type And Quantity
3 toggle
-
Maximum Continuous Load Current Rating Per Pole
3.5 amperes ac second location
-
Case Material
plastic
-
Body Width
2.260 inches maximum
-
Fragility Factor
moderately rugged
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Inclosure Protection Type For Which Designed
salt spray proof and vibration resistant and shock resistant and fungus proof
-
Circuit Protection Type
overcurrent all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 ac all locations and 5000.0 dc all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.812 inches nominal
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Unpackaged Unit Weight
13.000 ounces
-
Internal Trip Release Configuration
series trip all locations
-
Operating Voltage Type And Rating Per Pole In Volts
120.0 ac all locations and 30.0 dc all locations
-
Thread Quantity Per Inch
32
-
Center To Center Distance Between Terminals Parallel To Length
1.188 inches nominal
-
Trip Release Method
magnetic-hydraulic all locations
-
Body Style
multipole-multiple actuator type