Technical Characteristics
-
Bushing Length
0.375 inches maximum
-
Pole Quantity
1
-
Case Material
metal
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Body Length
1.500 inches maximum
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Arc Quenching Method
magnetic blowout
-
Body Style
single pole type
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Main Contact Tripping Mechanism Type
nontrip free
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Operating Voltage Type And Rating Per Pole In Volts
110.0 ac single location
-
Circuit Protection Type
overcurrent single location
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac single location
-
Nominal Thread Size
0.375 inches
-
Actuator Function
trip-reset
-
Storage Type
general purpose warehouse
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Reset Method
manual
-
Special Handling Feature
magnetic
-
Terminal Type And Quantity
2 wire hook
-
Trip Release Method
magnetic single location
-
Fragility Factor
moderately rugged
-
~1
single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 ac single location
-
Thread Series Designator
unef
-
Frequency In Hertz
60.0 single location
-
Mounting Surface To Terminal End Distance
1.605 inches maximum
-
Body Width
0.625 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.500 maximum at 200 pct single location and 0.100 minimum at 200 pct single location and 0.020 minimum at 300 pct single location and 0.010 minimum at 400 pct single location and 0.130 maximum at 300 pct single location and 0.050 maximum at 400 pct