74-930A

Circuit Breakers

CIRCUIT BREAKER

74-930A

5925-00-704-2295

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Center To Center Distance Between Terminals Parallel To Width

    0.740 inches minimum and 0.760 inches maximum

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    1.802 inches minimum and 1.822 inches maximum

  • Terminal Type And Quantity

    6 screw

  • Maximum Continuous Load Current Rating Per Pole

    1.5 amperes ac third location

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    0.740 inches minimum and 0.760 inches maximum

  • Frequency In Hertz

    400.0 all locations

  • Center To Center Distance Between Terminals Parallel To Length

    1.180 inches minimum and 1.200 inches maximum

  • Body Length

    2.490 inches minimum and 2.510 inches maximum

  • Manual Actuator Type And Quantity

    3 toggle

  • Operating Voltage Type And Rating Per Pole In Volts

    200.0 ac all locations

  • Case Material

    plastic

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac all locations

  • Thread Quantity Per Inch

    32

  • Trip Release Method

    magnetic all locations

  • Body Style

    multipole-multiple actuator type

  • Body Width

    2.263 inches minimum and 2.283 inches maximum

  • Mounting Surface To Terminal End Distance

    1.990 inches minimum and 2.010 inches maximum

  • Maximum Continuous Load Current Rating Per Pole

    1.5 amperes ac second location

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    150.0 all locations

  • Nominal Thread Size

    0.138 inches

  • Fragility Factor

    moderately rugged

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Inclosure Protection Type For Which Designed

    dustproof

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Trip Delay Time In Seconds Per Rated Continuous Current

    17.000 minimum at 200 pct all locations and 58.000 maximum at 200 pct all locations

  • Maximum Continuous Load Current Rating Per Pole

    2.5 amperes ac first location

  • Storage Type

    general purpose warehouse

  • Trip Release Characteristic

    time delay all locations

  • Actuator Function

    trip-reset

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Internal Trip Release Configuration

    series trip all locations

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.