135490-002
Circuit Breakers
CIRCUIT BREAKER
135490-002
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Inclosure Protection Type For Which Designed
explosion resistant
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.130 minimum at 200 pct and 0.400 maximum at 200 pct and 0.040 minimum at 300 pct and 0.120 maximum at 300 pct and 0.025 minimum at 300 pct and 0.070 maximum at 400 pct
-
Actuator Position Designation
at pole one
-
Actuator Function
trip-reset
-
Main Contact Tripping Mechanism Type
trip free
-
Reset Method
manual
-
Ultimate Trip Time Per Pole In Seconds
0.280 minimum and 1.800 maximum
-
Trip Release Characteristic
time delay
-
Trip Release Method
magnetic-hydraulic
-
Circuit Protection Type
overcurrent
-
Operating Voltage Type And Rating Per Pole In Volts
32.0 dc
-
Mounting Facility Type And Quantity
2 threaded hole
-
Center To Center Distance Between Terminals Parallel To Length
1.190 inches nominal
-
Body Width
0.750 inches nominal
-
Body Length
2.500 inches nominal
-
Terminal Type And Quantity
2 screw
-
Thread Series Designator
unc
-
Nominal Thread Size
0.138 inches
-
Internal Trip Release Configuration
series trip
-
Manual Actuator Type And Quantity
1 toggle
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3000.0 dc
-
Maximum Continuous Load Current Rating Per Pole
2.0 amperes dc
-
Thread Quantity Per Inch
32
-
Pole Quantity
1
-
Mounting Surface To Terminal End Distance
2.000 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.812 inches nominal
-
Case Material
plastic