9174560
Circuit Breakers
CIRCUIT BREAKER
9174560
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Boss Height
0.156 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Mounting Surface To Terminal End Distance
3.310 inches maximum
-
Frequency In Hertz
400.0 all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
2.062 inches nominal
-
Manual Actuator Type And Quantity
3 toggle
-
Body Width
3.062 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
2.062 inches nominal
-
Case Material
plastic
-
Terminal Type And Quantity
6 threaded stud
-
Actuator Function
trip-reset
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Internal Trip Release Configuration
series trip all locations
-
Thread Quantity Per Inch
32
-
Center To Center Distance Between Terminals Parallel To Length
3.062 inches nominal
-
Trip Release Method
magnetic all locations
-
Body Style
multipole-multiple actuator type
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Mounting Facility Type And Quantity
6 threaded hole
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac all locations
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
14.000 minimum at 150 pct all locations and 2.000 minimum at 300 pct all locations and 20.000 maximum at 200 pct all locations and 50.000 maximum at 150 pct all locations and 6.000 minimum at 200 pct all locations and 6.500 maximum at 300 pct all
-
~1
locations
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Body Length
3.790 inches maximum
-
Thread Series Designator
unc
-
Operating Voltage Type And Rating Per Pole In Volts
416.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1300.0 ac single location
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Trip Release Characteristic
time delay all locations