260-1311-00
Circuit Breakers
CIRCUIT BREAKER
260-1311-00
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Center To Center Distance Between Terminals Parallel To Length
1.938 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.062 inches nominal
-
Terminal Type And Quantity
2 threaded stud
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Body Length
2.500 inches nominal
-
Boss Height
0.140 inches nominal
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 maximum at 200 pct single location and 2.000 maximum at 200 pct single location and 0.300 maximum at 300 pct single location and 0.170 maximum at 400 pct single location
-
Body Style
single pole type
-
Frequency In Hertz
60.0 single location
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac single location and 50.0 dc single location
-
Case Material
plastic
-
Actuator Function
reset
-
Trip Release Method
magnetic single location
-
Thread Series Designator
unc
-
Reset Method
manual
-
Body Width
0.750 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
3.0 amperes ac single location and 3.0 amperes dc single location
-
Mounting Facility Type And Quantity
2 threaded hole
-
Inclosure Protection Type For Which Designed
fungus resistant and hermetically sealed
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac single location and 2000.0 dc single location
-
Pole Quantity
1
-
Manual Actuator Type And Quantity
1 toggle
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Mounting Surface To Terminal End Distance
2.471 inches nominal