6752-302-10
Circuit Breakers
CIRCUIT BREAKER
6752-302-10
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Width
2.250 inches maximum
-
Fragility Factor
moderately rugged
-
Special Handling Feature
magnetic
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.782 inches minimum and 1.842 inches maximum
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Switch Location And Position Designation
internal at pole three
-
Switch Terminal Type
turret
-
Storage Type
general purpose warehouse
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Unpackaged Unit Weight
2.100 pounds
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Thread Quantity Per Inch
32
-
Center To Center Distance Between Terminals Parallel To Length
1.158 inches minimum and 1.218 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
10.000 minimum at 200 pct all locations and 75.000 maximum at 200 pct all locations
-
Trip Release Method
thermal-magnetic all locations
-
Body Height
2.440 inches minimum and 2.500 inches maximum
-
Switch Contact Arrangement
single pole, double throw
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant
-
Mounting Facility Type And Quantity
6 threaded hole
-
Body Style
multipole-single actuator type
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.490 inches minimum and 1.510 inches maximum
-
Body Length
2.189 inches maximum
-
Nominal Thread Size
0.138 inches
-
Main Contact Tripping Mechanism Type
trip free
-
Maximum Continuous Load Current Rating Per Pole
10.0 amperes ac all locations and 10.0 amperes dc all locations
-
Trip Release Ambient Temp Rating
40.0 deg celsius maximum all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
4200.0 ac all locations and 6000.0 dc all locations
-
Switch Voltage Rating And Type In Volts
28.0 dc
-
Switch Current Rating And Type In Amps
7.0 dc
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
138.0 all locations
-
Bushing Length
0.235 inches minimum and 0.250 inches maximum
-
Operating Voltage Type And Rating Per Pole In Volts
205.0 ac all locations and 28.0 dc all locations
-
Center To Center Distance Between Terminals Parallel To Width
1.490 inches minimum and 1.510 inches maximum
-
Frequency In Hertz
400.0 all locations
-
Auxiliary Switch Function And Quantity
1 alarm
-
Terminal Type And Quantity
6 tab w/screw
-
Manual Actuator Type And Quantity
3 toggle
-
Case Material
plastic