3XAM1516MG3-8-250VAC1
Circuit Breakers
CIRCUIT BREAKER
3XAM1516MG3-8-250VAC1
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
locations
-
Inclosure Protection Type For Which Designed
fungus resistant and moisture resistant and explosion resistant
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Thread Series Designator
unc
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Body Length
3.719 inches nominal
-
Mounting Surface To Terminal End Distance
3.239 inches nominal
-
Trip Release Characteristic
time delay all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
300.000 maximum at 150 pct all locations and 10.000 minimum at 300 pct all locations and 35.000 minimum at 200 pct all locations and 80.000 minimum at 150 pct all locations and 100.000 maximum at 200 pct all locations and 30.000 maximum at 300 pct all
-
Terminal Type And Quantity
6 threaded stud
-
Case Material
plastic
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
1.031 inches nominal
-
Manual Actuator Type And Quantity
3 toggle
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.750 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
8.0 amperes ac all locations
-
Ultimate Trip Time Per Pole In Seconds
150.000 minimum all locations and 500.000 maximum all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Frequency In Hertz
60.0 all locations
-
Boss Height
0.156 inches nominal
-
Nominal Thread Size
0.138 inches
-
Mounting Facility Type And Quantity
6 threaded hole
-
Body Width
3.052 inches nominal
-
Center To Center Distance Between Terminals Parallel To Length
3.063 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Body Style
multipole-multiple actuator type
-
Trip Release Method
magnetic-hydraulic all locations
-
Thread Quantity Per Inch
32
-
Center To Center Distance Between Terminals Parallel To Width
1.031 inches nominal
-
Internal Trip Release Configuration
series trip all locations
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Actuator Function
trip-reset