3XAM1516MG3-8-91

Circuit Breakers

CIRCUIT BREAKER

3XAM1516MG3-8-91

5925-00-782-1361

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • ~1

    locations

  • Inclosure Protection Type For Which Designed

    fungus resistant and moisture resistant and explosion resistant

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Actuator Position Designation

    at each pole

  • Reset Method

    manual

  • Body Length

    3.719 inches nominal

  • Mounting Surface To Terminal End Distance

    3.239 inches nominal

  • Trip Release Characteristic

    time delay all locations

  • Trip Delay Time In Seconds Per Rated Continuous Current

    300.000 maximum at 150 pct all locations and 10.000 minimum at 300 pct all locations and 35.000 minimum at 200 pct all locations and 80.000 minimum at 150 pct all locations and 100.000 maximum at 200 pct all locations and 30.000 maximum at 300 pct all

  • Terminal Type And Quantity

    6 threaded stud

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.031 inches nominal

  • Manual Actuator Type And Quantity

    3 toggle

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.750 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    8.0 amperes ac all locations

  • Ultimate Trip Time Per Pole In Seconds

    150.000 minimum all locations and 500.000 maximum all locations

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac all locations

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1500.0 ac all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Frequency In Hertz

    60.0 all locations

  • Boss Height

    0.156 inches nominal

  • Nominal Thread Size

    0.138 inches

  • Mounting Facility Type And Quantity

    6 threaded hole

  • Body Width

    3.052 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    3.063 inches nominal

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0 all locations

  • Body Style

    multipole-multiple actuator type

  • Trip Release Method

    magnetic-hydraulic all locations

  • Thread Quantity Per Inch

    32

  • Center To Center Distance Between Terminals Parallel To Width

    1.031 inches nominal

  • Internal Trip Release Configuration

    series trip all locations

  • External Actuator Linkage Arrangement

    one, two, and three linked

  • Actuator Function

    trip-reset

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...