A116-800W2

Circuit Breakers

CIRCUIT BREAKER

A116-800W2

5925-00-782-6845

5925 - Circuit Breakers

Army United States Department Of The

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Boss Height

    0.240 inches minimum and 0.260 inches maximum

  • Terminal Type And Quantity

    1 clip and 1 compression

  • Body Height

    2.570 inches minimum and 2.590 inches maximum

  • Circuit Protection Type

    overcurrent single location

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    135.0 single location

  • Pole Quantity

    1

  • Manual Actuator Type And Quantity

    1 toggle

  • Trip Release Method

    thermal-magnetic single location

  • Trip Release Characteristic

    time delay single location

  • Trip Release Ambient Temp Rating

    25.0 deg celsius nominal single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Arc Quenching Method

    magnetic blowout

  • Body Style

    single pole type

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac single location

  • Mounting Facility Type And Quantity

    2 terminal

  • Frequency In Hertz

    60.0 single location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    120.000 maximum at 200 pct single location

  • Body Length

    2.990 inches minimum and 3.010 inches maximum

  • Body Width

    0.720 inches minimum and 0.740 inches maximum

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    10000.0 ac single location

  • Case Material

    plastic

  • Specification/Standard Data

    81348-w-c-375/1 government specification

  • Fragility Factor

    moderately rugged

  • Inclosure Protection Type For Which Designed

    moisture resistant

  • Operating Voltage Type And Rating Per Pole In Volts

    240.0 ac single location

  • Reset Method

    manual

  • Actuator Position Designation

    at pole one

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • ~1

    data on certain environmental and performance re

  • Test Data Document

    81348-w-c-375 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...