MIL-C-17361AQB-A50,1

Circuit Breakers

CIRCUIT BREAKER

MIL-C-17361AQB-A50,1

5925-00-783-6399

5925 - Circuit Breakers

Military Specifications

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    5000.0 ac all locations and 2500.0 dc all locations

  • Pole Quantity

    3

  • Circuit Protection Type

    overcurrent all locations

  • Thread Series Designator

    unc

  • Reset Method

    manual

  • Operating Voltage Type And Rating Per Pole In Volts

    500.0 ac all locations and 250.0 dc all locations

  • Case Material

    plastic

  • Body Length

    4.125 inches nominal

  • Body Height

    3.375 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    2.625 inches nominal

  • Thread Quantity Per Inch

    24

  • Boss Height

    0.125 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.125 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    2.938 inches nominal

  • Maximum Continuous Load Current Rating Per Pole

    10.0 amperes ac all locations and 10.0 amperes dc all locations

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    115.0 all locations

  • Main Contact Tripping Mechanism Type

    trip free

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    0.625 inches nominal

  • Frequency In Hertz

    60.0 all locations

  • Terminal Type And Quantity

    6 quick disconnect, female

  • Manual Actuator Type And Quantity

    1 toggle

  • Body Style

    multipole-single actuator type

  • Trip Release Ambient Temp Rating

    50.0 deg celsius nominal all locations

  • Trip Release Method

    thermal-magnetic all locations

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Trip Delay Time In Seconds Per Rated Continuous Current

    20.000 minimum at 200 pct all locations and 90.000 maximum at 200 pct all locations

  • Trip Release Characteristic

    instantaneous all locations and time delay all locations

  • Actuator Position Designation

    at pole one and at pole three

  • Body Width

    3.344 inches nominal

  • Actuator Function

    trip-reset

  • Nominal Thread Size

    0.216 inches

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...