CF3BM090
Circuit Breakers
CIRCUIT BREAKER
CF3BM090
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Pole Quantity
3
-
Circuit Protection Type
overcurrent all locations
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Actuator Function
trip-reset
-
Maximum Continuous Load Current Rating Per Pole
90.0 amperes ac all locations and 90.0 amperes dc all locations
-
Internal Trip Release Configuration
series trip all locations
-
Trip Release Characteristic
instantaneous all locations and time delay all locations
-
Operating Voltage Type And Rating Per Pole In Volts
600.0 ac all locations and 250.0 dc all locations
-
Mounting Facility Type And Quantity
4 threaded hole
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.240 nominal at 200 pct all locations
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Ultimate Trip Time Per Pole In Seconds
0.360 nominal all locations
-
Manual Actuator Type And Quantity
1 toggle
-
Terminal Type And Quantity
6 quick disconnect, female
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
100000.0 ac all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Nominal Thread Size
0.250 inches
-
Case Material
plastic
-
Trip Release Method
thermal all locations