4570446G20
Circuit Breakers
TRIPPER,CIRCUIT BREAKER
4570446G20
TRIPPER,CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Trip Release Method
thermal all locations
-
Ultimate Trip Time Per Pole In Seconds
3600.000 nominal all locations
-
Operating Voltage Type And Rating Per Pole In Volts
500.0 ac all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
100.000 minimum at 200 pct all locations and 300.000 maximum at 200 pct all locations
-
End Item Identification
used in circuit breaker nsn 5925-01-075-8931 onboard 270 ft. wmec coast guard vessels
-
Overall Width
8.250 inches nominal
-
Frequency In Hertz
400.0 all locations
-
Unthreaded Mounting Hole Diameter
0.375 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
150.0 amperes ac all locations
-
Terminal Type And Quantity
6 screw
-
Overall Length
4.500 inches nominal
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0 all locations
-
Overall Height
4.500 inches nominal
-
Trip Release Ambient Temp Rating
50.0 deg celsius nominal all locations
-
Mounting Facility Type And Quantity
3 unthreaded hole
-
Adjustable Trip Setting Current Range Per Pole In Amps
+625.0/+1300.0 ac all locations
-
Internal Trip Release Configuration
series trip all locations
-
Trip Release Characteristic
time delay all locations
-
Features Provided
adjustable trip release
-
Body Style
rectangular dimensional envelope
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3