3XAM17-5-208AC400-56
Circuit Breakers
CIRCUIT BREAKER
3XAM17-5-208AC400-56
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Length
2.500 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.812 inches nominal
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.750 inches nominal
-
Mounting Surface To Terminal End Distance
2.000 inches nominal
-
Pole Quantity
3
-
Mounting Facility Type And Quantity
6 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
3500.0 ac
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
150.0
-
Manual Actuator Type And Quantity
3 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at each pole
-
External Actuator Linkage Arrangement
one,two,and three linked
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.280 minimum at 200 pct and 0.900 maximum at 200 pct
-
Inclosure Protection Type For Which Designed
explosion resistant
-
Frequency In Hertz
400.0
-
Thread Series Designator
unc
-
Bushing Length
any acceptable
-
Body Width
2.273 inches nominal
-
Case Material
plastic
-
Center To Center Distance Between Terminals Parallel To Length
1.190 inches nominal
-
Center To Center Distance Between Terminals Parallel To Width
0.750 inches nominal
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac
-
Operating Voltage Type And Rating Per Pole In Volts
208.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic-hydraulic
-
Trip Release Characteristic
time delay
-
Ultimate Trip Time Per Pole In Seconds
1.000 minimum and 4.000 maximum
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Terminal Type And Quantity
6 screw