Technical Characteristics
-
Manual Actuator Type And Quantity
1 toggle
-
Main Contact Tripping Mechanism Type
trip free
-
Reset Method
manual
-
Trip Release Characteristic
time delay all locations
-
Circuit Protection Type
overcurrent all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1500.0 ac all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Maximum Continuous Load Current Rating Per Pole
4.0 amperes ac all locations
-
Mounting Facility Type And Quantity
8 threaded hole
-
Pole Quantity
4
-
Overall Width
3.060 inches nominal
-
Overall Height
2.530 inches nominal
-
Overall Length
3.330 inches nominal
-
Actuator Function
trip-reset
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.900 minimum at 150 pct and
-
Special Features
pole no. 4 provided with relay-trip
-
Frequency In Hertz
400.0 all locations
-
Body Style
1d rectangular dimensional envelope
-
Case Material
plastic
-
Thread Quantity Per Inch
32
-
Trip Release Method
magnetic-hydraulic all locations
-
Nominal Thread Size
0.138 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.080 minimum at 300 pct and
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.600 minimum at 200 pct and
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.700 maximum at 300 pct all locations
-
Trip Delay Time In Seconds Per Rated Continuous Current
4.000 maximum at 200 pct and
-
Trip Delay Time In Seconds Per Rated Continuous Current
7.000 maximum at 150 pct and
-
Thread Series Designator
unc
-
Terminal Type And Quantity