NEF213030

Circuit Breakers

CIRCUIT BREAKER

NEF213030

5925-00-856-3629

5925 - Circuit Breakers

Challenger Electrical Equipment Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    5.125 inches nominal

  • Mounting Slot Width

    0.375 inches nominal

  • Body Length

    6.219 inches nominal

  • Body Width

    1.375 inches nominal

  • Pole Quantity

    1

  • Manual Actuator Type And Quantity

    1 toggle

  • Trip Release Method

    thermal-magnetic single location

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.000 inches nominal

  • Trip Release Characteristic

    time delay single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Center To Center Distance Between Terminals Parallel To Length

    5.219 inches nominal

  • Inclosure Protection Type For Which Designed

    general purpose

  • Body Style

    single pole type

  • Frequency In Hertz

    60.0 single location

  • Terminal Type And Quantity

    2 compression

  • Boss Height

    0.203 inches nominal

  • Body Height

    3.406 inches nominal

  • Case Material

    plastic

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    140.0 single location

  • Mounting Facility Type And Quantity

    4 slot

  • Reset Method

    manual

  • Actuator Position Designation

    at pole one

  • Maximum Continuous Load Current Rating Per Pole

    30.0 amperes ac single location and 30.0 amperes dc single location

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal single location

  • Operating Voltage Type And Rating Per Pole In Volts

    277.0 ac single location and 125.0 dc single location

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    14000.0 ac single location and 10000.0 dc single location

  • Circuit Protection Type

    overcurrent single location

  • Trip Delay Time In Seconds Per Rated Continuous Current

    12.000 minimum at 200 pct single location and 35.000 maximum at 200 pct single location

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...