APL111-30-1
Circuit Breakers
CIRCUIT BREAKER
APL111-30-1
Sensata Technologies Maryland Inc
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Fragility Factor
moderately rugged
-
Maximum Continuous Load Current Rating Per Pole
5.0 amperes ac first location
-
Terminal Type And Quantity
6 threaded stud
-
Case Material
plastic
-
Manual Actuator Type And Quantity
3 toggle
-
Thread Pitch Diameters
+0.1177/+0.1214 inches
-
Frequency In Hertz
400.0 all locations
-
Operating Voltage Type And Rating Per Pole In Volts
250.0 ac all locations
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width
0.740 inches minimum and 0.760 inches maximum
-
Test Data Document
24930-g330024 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)
-
Body Width
2.280 inches maximum
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
3
-
Special Handling Feature
magnetic
-
Center To Center Distance Between Terminals Parallel To Length
1.924 inches minimum and 1.952 inches maximum
-
Inclosure Protection Type For Which Designed
moisture resistant and shock resistant and vibration resistant
-
Arc Quenching Method
magnetic blowout
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
115.0 all locations
-
Main Contact Tripping Mechanism Type
trip free
-
Center To Center Distance Between Terminals Parallel To Width
0.740 inches minimum and 0.760 inches maximum
-
Nominal Thread Size
0.138 inches
-
Mounting Facility Type And Quantity
6 threaded hole
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.200 minimum at 200 pct all locations and 0.800 maximum at 200 pct all locations
-
Unpackaged Unit Weight
0.875 pounds
-
Body Style
multipole-multiple actuator type
-
Trip Release Method
magnetic all locations
-
Boss Height
0.155 inches maximum
-
Thread Quantity Per Inch
32
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
2.050 inches minimum and 2.070 inches maximum
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac third location
-
Body Length
2.530 inches maximum
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
1000.0 ac all locations
-
Internal Trip Release Configuration
series trip all locations
-
External Actuator Linkage Arrangement
one, two, and three linked
-
Mounting Surface To Terminal End Distance
2.570 inches minimum and 2.690 inches maximum
-
Actuator Function
trip-reset
-
Trip Release Characteristic
time delay all locations
-
Storage Type
general purpose warehouse
-
Reset Method
manual
-
Actuator Position Designation
at each pole
-
Thread Series Designator
unc
-
Maximum Continuous Load Current Rating Per Pole
25.0 amperes ac second location