3006279-07
Circuit Breakers
CIRCUIT BREAKER
3006279-07
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Thread Series Designator
unc
-
Terminal Type And Quantity
2 threaded stud
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes dc
-
Operating Voltage Type And Rating Per Pole In Volts
32.0 dc
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Function
trip-reset
-
Actuator Position Designation
at pole one
-
Switch Terminal Type
tab,solder lug
-
Case Material
plastic
-
Pole Quantity
1
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
5000.0 dc
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic
-
Auxiliary Switch Function And Quantity
1 control
-
Internal Trip Release Configuration
series trip
-
Nominal Thread Size
0.138 inches
-
Switch Location And Position Designation
external at pole one
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.180 minimum at 200 pct and 0.650 maximum at 200 pct and 0.060 minimum at 300 pct and 0.280 maximum at 300 pct and 0.030 minimum at 400 pct and 0.120 maximum at 400 pct