2315741P19
Circuit Breakers
CIRCUIT BREAKER
2315741P19
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Body Style
1b multipole-single actuator type
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Maximum Continuous Load Current Rating Per Pole
15.0 amperes dc all locations
-
Circuit Protection Type
overcurrent all locations
-
Trip Release Method
magnetic all locations
-
Ultimate Trip Time Per Pole In Seconds
2.400 minimum and 42.000 maximum all locations
-
Reset Method
manual
-
Actuator Position Designation
at each pole
-
Nominal Thread Size
0.375 inches
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Special Test Features
navord od36190
-
Bushing Length
0.340 inches nominal
-
Body Length
1.531 inches nominal
-
Body Width
1.250 inches nominal
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Mounting Surface To Terminal End Distance
1.855 inches nominal
-
Pole Quantity
2
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
50.0 dc all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
500.0 dc all locations
-
Trip Release Characteristic
time delay all locations
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Main Contact Tripping Mechanism Type
trip free
-
Manual Actuator Type And Quantity
1 toggle
-
Reference Number Differentiating Characteristics
as differentiated by special test features
-
Terminal Type And Quantity
4 wire hook
-
Thread Series Designator
unef
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.580 minimum at 200 pct and 6.000 maximum at 200 pct and 0.080 minimum at 300 pct and 1.600 maximum at 300 pct and 0.010 minimum at 400 pct and 0.630 maximum at 400 pct all locations
-
Internal Trip Release Configuration
series trip all locations
-
Actuator Function
reset