ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Mounting Surface To Terminal End Distance
2.234 inches maximum
-
Bushing Length
0.250 inches nominal
-
Thread Series Designator
unc
-
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length
1.812 inches nominal
-
Reset Method
manual
-
Actuator Position Designation
at pole one
-
Actuator Function
trip-reset
-
Terminal Type And Quantity
2 screw
-
Mounting Facility Type And Quantity
2 threaded hole
-
Thread Quantity Per Inch
32
-
Circuit Protection Type
overcurrent single location
-
Center To Center Distance Between Terminals Parallel To Length
1.437 inches nominal
-
Trip Release Method
thermal single location
-
Manual Actuator Type And Quantity
1 push-pull
-
Pole Quantity
1
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
2500.0 ac single location and 3000.0 dc single location
-
Internal Trip Release Configuration
series trip single location
-
Nominal Thread Size
0.138 inches
-
Operating Voltage Type And Rating Per Pole In Volts
115.0 ac single location and 28.0 dc single location
-
Trip Release Characteristic
time delay single location
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0 single location
-
Main Contact Tripping Mechanism Type
trip free
-
Body Style
single pole type
-
Body Length
2.187 inches maximum
-
Trip Delay Time In Seconds Per Rated Continuous Current
15.000 minimum at 200 pct single location and 60.000 maximum at 200 pct single location
-
Trip Release Ambient Temp Rating
40.0 deg celsius maximum single location
-
Maximum Continuous Load Current Rating Per Pole
125.0 amperes ac single location and 125.0 amperes dc single location
-
Frequency In Hertz
60.0 single location
-
Body Width
1.000 inches maximum
-
Case Material
plastic