2315742P49
Circuit Breakers
CIRCUIT BREAKER
2315742P49
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
Bushing Length
0.340 inches nominal
-
Body Length
1.531 inches nominal
-
Body Width
1.250 inches nominal
-
Case Material
metal
-
Center To Center Distance Between Terminals Parallel To Width
0.625 inches nominal
-
Mounting Surface To Terminal End Distance
1.855 inches nominal
-
Pole Quantity
2
-
Mounting Facility Type And Quantity
1 threaded bushing w/panel seal
-
Maximum Continuous Load Current Rating Per Pole
1.5 amperes ac
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
300.0 ac
-
Circuit Protection Type
overcurrent
-
Trip Release Method
magnetic
-
Ultimate Trip Time Per Pole In Seconds
0.530 minimum and 5.600 maximum
-
Main Contact Tripping Mechanism Type
trip free
-
Actuator Function
reset
-
Internal Trip Release Configuration
series trip
-
Inclosure Protection Type For Which Designed
hermetically sealed
-
Thread Series Designator
unef
-
Terminal Type And Quantity
4 wire hook
-
Reference Number Differentiating Characteristics
as differentiated by special test features
-
Center To Center Distance Between Terminals Parallel To Length
0.875 inches nominal
-
Thread Quantity Per Inch
32
-
Operating Voltage Type And Rating Per Pole In Volts
230.0 ac
-
Trip Release Characteristic
time delay
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
125.0
-
Reset Method
manual
-
Manual Actuator Type And Quantity
1 toggle
-
Actuator Position Designation
at each pole
-
Nominal Thread Size
0.375 inches
-
Trip Delay Time In Seconds Per Rated Continuous Current
0.120 minimum at 200 pct and 1.300 maximum at 200 pct and 0.030 minimum at 300 pct and 0.450 maximum at 300 pct and 0.010 minimum at 400 pct and 0.220 maximum at 400 pct
-
Frequency In Hertz
400.0
-
Special Test Features
navord od36190