W-C-375/06-004
Circuit Breakers
CIRCUIT BREAKER
W-C-375/06-004
CIRCUIT BREAKER
ACT NOW! SUBMIT A QUICK QUOTE.
Technical Characteristics
-
~1
data on certain environmental and performance re
-
Boss Height
0.188 inches nominal
-
Main Contact Tripping Mechanism Type
trip free
-
Test Data Document
81348-w-c-375 specification (includes engineering type bulletins, brochures,etc., that reflect specification type data in specification format; excludes commercial catalogs, industry directories, and similar trade publications, reflecting general type
-
Maximum Continuous Load Current Rating Per Pole
30.0 amperes ac all locations
-
Body Length
2.987 inches minimum and 3.013 inches maximum
-
Manual Actuator Type And Quantity
2 toggle
-
Mounting Facility Type And Quantity
2 terminal
-
Inclosure Protection Type For Which Designed
corrosion resistant
-
Terminal Type And Quantity
4 clip
-
Case Material
plastic
-
Specification/Standard Data
81348-w-c-375/6 government specification
-
Special Handling Feature
magnetic
-
Circuit Protection Type
overcurrent all locations
-
Pole Quantity
2
-
Actuator Position Designation
at each pole
-
Reset Method
manual
-
Storage Type
general purpose warehouse
-
Body Height
2.312 inches nominal
-
Trip Release Ambient Temp Rating
40.0 deg celsius nominal all locations
-
Trip Release Characteristic
time delay all locations
-
Actuator Function
trip-reset
-
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent
135.0 all locations
-
Operating Voltage Type And Rating Per Pole In Volts
240.0 ac all locations
-
Center To Center Distance Between Terminals Parallel To Width
0.552 inches minimum and 0.578 inches maximum
-
Body Style
multipole-multiple actuator type
-
Trip Delay Time In Seconds Per Rated Continuous Current
2.000 maximum at 200 pct all locations
-
Body Width
1.464 inches minimum and 1.496 inches maximum
-
Trip Release Method
thermal-magnetic all locations
-
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps
10000.0 ac all locations
-
Frequency In Hertz
60.0 all locations
-
Fragility Factor
moderately rugged