1922-5004

Circuit Breakers

CIRCUIT BREAKER

1922-5004

5925-00-914-8879

5925 - Circuit Breakers

Jaidinger Mfg. Co. Inc.

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Body Width

    4.125 inches nominal

  • Body Height

    3.380 inches nominal

  • Center To Center Distance Between Terminals Parallel To Length

    5.250 inches nominal

  • Center To Center Distance Between Terminals Parallel To Width

    1.375 inches nominal

  • Unthreaded Mounting Hole Diameter

    0.188 inches nominal

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    4.880 inches nominal

  • Boss Height

    0.125 inches nominal

  • Pole Quantity

    3

  • Mounting Facility Type And Quantity

    4 unthreaded hole

  • Trip Release Method

    thermal-magnetic

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    125.0

  • Ultimate Trip Time Per Pole In Seconds

    750.000 minimum and 1000.000 maximum

  • Reset Method

    manual

  • Manual Actuator Type And Quantity

    1 toggle

  • Actuator Function

    trip-reset

  • Inclosure Protection Type For Which Designed

    general purpose

  • Trip Release Ambient Temp Rating

    40.0 deg celsius nominal

  • Terminal Type And Quantity

    6 compression

  • Body Length

    6.310 inches nominal

  • Case Material

    plastic

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Width

    1.380 inches nominal

  • Storage Type

    general purpose warehouse

  • Maximum Continuous Load Current Rating Per Pole

    100.0 amperes ac

  • Operating Voltage Type And Rating Per Pole In Volts

    480.0 ac

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    15000.0 ac

  • Circuit Protection Type

    overcurrent

  • Trip Release Characteristic

    instantaneouss and time delay

  • Main Contact Tripping Mechanism Type

    trip free

  • Actuator Position Designation

    at pole two

  • Trip Delay Time In Seconds Per Rated Continuous Current

    1.800 maximum at 200 pct

  • Frequency In Hertz

    60.0

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...