AM12HKMG6-0-125-250VAC60C5

Circuit Breakers

CIRCUIT BREAKER

AM12HKMG6-0-125-250VAC60C5

5925-00-919-1771

5925 - Circuit Breakers

Eaton Corp

CIRCUIT BREAKER

ACT NOW! SUBMIT A QUICK QUOTE.

Technical Characteristics

  • Test Data Document

    13499-260-4021 drawing (this is the basic governing drawing, such as a contractor drawing, original equipment manufacturer drawing, etc.; excludes any specification, standard or other document that may be referenced in a basic governing drawing)

  • Inclosure Protection Type For Which Designed

    dustproof and sand resistant and salt spray proof and humidity resistant and explosion proof and vibrationproof

  • Body Width

    0.755 inches minimum and 0.770 inches maximum

  • Storage Type

    general purpose warehouse

  • Actuator Function

    trip-reset

  • Body Length

    2.530 inches maximum

  • Mounting Facility Type And Quantity

    2 threaded hole

  • Distance Between Centerlines Of Mounting Facilities Parallel To Body Length

    2.050 inches minimum and 2.070 inches maximum

  • Thread Quantity Per Inch

    32

  • Center To Center Distance Between Terminals Parallel To Length

    1.950 inches minimum and 1.970 inches maximum

  • Circuit Protection Type

    overcurrent single location

  • Operating Voltage Type And Rating Per Pole In Volts

    250.0 ac single location

  • Switch Contact Arrangement

    single pole, double throw

  • Switch Current Rating And Type In Amps

    2.5 ac and 1.0 dc

  • Switch Voltage Rating And Type In Volts

    250.0 ac and 50.0 dc

  • Pole Quantity

    1

  • Manual Actuator Type And Quantity

    1 toggle

  • Internal Trip Release Configuration

    series trip single location

  • Nominal Thread Size

    0.138 inches

  • Trip Release Characteristic

    time delay single location

  • Main Contact Tripping Mechanism Type

    trip free

  • Trip Delay Time In Seconds Per Rated Continuous Current

    0.250 minimum at 200 pct single location and 0.700 maximum at 200 pct single location

  • Arc Quenching Method

    magnetic blowout

  • Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent

    115.0 single location

  • Body Style

    single pole type

  • Unpackaged Unit Weight

    4.250 ounces

  • Boss Height

    0.145 inches minimum and 0.160 inches maximum

  • Frequency In Hertz

    60.0 single location

  • Thread Pitch Diameters

    +0.1177/+0.1214 inches

  • Auxiliary Switch Function And Quantity

    1 alarm

  • Switch Location And Position Designation

    internal at pole one

  • Case Material

    plastic

  • Terminal Type And Quantity

    2 threaded stud

  • Fragility Factor

    moderately rugged

  • Trip Release Method

    magnetic single location

  • Maximum Continuous Load Current Rating Per Pole

    125.0 milliamperes ac single location

  • Switch Terminal Type

    tab, solder lug

  • Special Handling Feature

    magnetic

  • Mounting Surface To Terminal End Distance

    2.900 inches maximum

  • Thread Series Designator

    unc

  • Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps

    1000.0 ac single location

  • Reset Method

    manual

  • Actuator Position Designation

    at pole one

Certified to
AS6081 Methods

Implementing Quality Procurement

A rigorous vendor selection process and vendor management system are essential to ensuring quality.
Read more...

Supplying Quality Products

We take every measure to ensure that we supply quality, authentic parts including a strict vendor selection process and rigorous product inspections..
Read more...

Providing Quality People

Our team of dedicated account managers, procurement professionals and specialized inspectors is the most valuable resource we have.
Read more...